Description

Double-walled, circular corrugated pipe in 100% food-grade HDPE with insulation in expanded PE material. Internal antibacterial, antistatic and antifungal treatment of the pipe. Tube with smooth internal surface.

Features

Internal ripple <5%.

Storage temperature -30°C + 60°C.

Installation temperature -5°C +60°C.

Use

Controlled mechanical ventilation. Connection from the distribution boxes to the plenums of the vents and grills.

Technical Specifications

 HTPEHTPE
ISOLPLUS 63ISOLPLUS 76
External Diameter of the Non-Insulated Corrugated Ductmm7590
Internal Diameter of the Non-Insulated Corrugated Ductmm6376
External Diameter of the Insulated Corrugated Ductmm87102
Weightgr/m320420
Crush Resistance CEI EN 61386-24N>450>450
Crush Resistance EN 17192N>250>250
Ring StiffnessSN>8>8
Bending Radiusmm225270
Internal Corrugation-<5%<5%
Insulation Layer Densitykg/m33030
Thermal Conductivity of the Insulation LayerW/mK0,036 (10°C)0,036 (10°C)

Pressure Drops

 HTPEHTPE
ISOLPLUS 63ISOLPLUS 76
Airflow Rate at 2 m/s Velocitym³/h22,4432,66
Pressure Drop at 2 m/s VelocityPressure Drop – Straight Duct (1 m)Pa1,040,99
Pressure Drop – Bend 90°Pa0,790,87
Pressure Drop – Bend 180°Pa1,301,32
Airflow Rate at 2,5 m/s Velocitym³/h28,0640,83
Pressure Drop at 2,5 m/s VelocityPressure Drop – Straight Duct (1 m)Pa1,621,54
Pressure Drop – Bend 90°Pa1,241,35
Pressure Drop – Bend 180°Pa2,032,07
Airflow Rate at 3 m/s Velocitym³/h33,6748,99
Pressure Drop at 3 m/s VelocityPressure Drop – Straight Duct (1 m)Pa2,332,22
Pressure Drop – Bend 90°Pa1,791,95
Pressure Drop – Bend 180°Pa2,932,98

Price List

ModelsRoll (m)Eur/Roll
HTPE ISOLPLUS 6325473,95
HTPE ISOLPLUS 7625592,44

DescriptionEuro
C90H – 90° PVC bend for HTPE PLUS corrugated duct Ø 63/75 mm.16,87