Descrizione

EVSLC-MF is a recessed fan coil unit designed to work in combination with a heat pump, providing optimal heating and cooling for both residential and commercial spaces. The unit features an onboard electronic controller capable of managing different temperature setpoints for heating or cooling within the same season, for 2 to 5 zones depending on the selected model.

Features

The EVSLC-MF features compact dimensions, allowing for easy recessed installation either on the ceiling or wall. The unit is built with a self-supporting galvanized steel frame with internal thermal and acoustic insulation, a hydronic coil appropriately sized to ensure satisfactory heat exchange, and a low-pressure-loss, easily removable filter section.

Each unit is equipped with energy-efficient EC centrifugal fans with forward-curved blades for optimal quiet operation (one fan per zone, depending on the selected model). The motors operate at constant airflow, enabling automatic adaptation to the installed system.

Four different sizes are available, offering varying heating and cooling capacities to allow the best selection based on system requirements.

Elettronica di comando

Version IN2: equipped with an electronic board for 3-speed fan control. Wall-mounted touch remote panel installed in a 503 junction box. Temperature sensors are located on the unit to manage the hydronic coil valve.

For each unit, a display must be purchased for each zone to be controlled, depending on the selected model, in order to achieve different temperature setpoints. For very large spaces, a single display can be used to maintain the same temperature setpoint throughout the area.

Available displays for these units:

  • EVCNV2-N: advanced remote control with integrated sensors, black.
  • EVCNV2-B: advanced remote control with integrated sensors, white.
  • EVCNW2-N: advanced remote control with integrated sensors and Wi-Fi, black.
  • EVCNW2-B: advanced remote control with integrated sensors and Wi-Fi, white.

Technical Features

  • (1) Coil water temperature 7/12 °C, ambient air temperature 27 °C dry bulb / 19 °C wet bulb (EU Regulation 2016/2281).
  • (2) Coil water temperature 45/40 °C, ambient air temperature 20 °C (EU Regulation 2016/2281).
  • (3) Data according to standards UNI EN 3741 and UNI EN 3744.

EVSLC-MF6080100120
Number of Controllable Zones2345
Nominal Airflow at Maximum Speedm3/h60090012001500
Airflow per Single Fan at Maximum Speedm3/h300
Airflow per Single Fan at Medium Speedm3/h205
Portata aria per singolo ventilatore alla min velocitàm3/h60
Available PressurePa100
Rated Power Consumption of FanskW0,140,210,280,35
Heating / Cooling Performance6080100120
Total Cooling Capacity 1kW3,85,57,28,1
Sensible Cooling Capacity 1kW2,73,95,16,1
Water Flow Ratem3/h0,600,951,21,4
Pressure DropkPa29211911
Maximum Total Cooling Capacity per ZonekW2,1
Maximum Sensible Cooling Capacity per ZonekW1,5
Total Cooling Capacity 2kW3,95,77,429,0
Water Flow Ratem3/h0,810,981,31,57
Pressure DropkPa29222112
Maximum Total Heating Capacity per ZonekW2,2
Acoustic Data 36080100120
Sound Power Lw Transmitted Through the StructuredB(A)60616264
Sound Power Lw Radiated into the DuctdB(A)65696971
Average Sound Pressure Level Lp at 1 mdB(A)46484951
Average Sound Pressure Level Lp at 3 mdB(A)38404143
Electrical data6080100120
Power SupplyV / ph / Hz230 / 1 / 50
Maximum Power ConsumptionkW0,190,280,370,46
Maximum Current DrawA0,71,42,12,8

Dimensions

  • All dimensions are expressed in mm.
  • Configurazione standard, attacchi batteria ad acqua a SINISTRA rispetto il flusso dell'aria.
  • A richiesta attacchi batteria ad acqua a DESTRA rispetto il flusso dell'aria.

ModelsABCDEFHø Mandata Aria DNReturn AirWater Connections IN/OUTCondensate Drain Ø mmNumber of Electrical Panels QEWeight Kg
b x h
EVSLC-MF 60790750240695770632902x160630x1503/4''F16/20243
EVSLC-MF 80990950240695970632903x160830x1503/4''F16/20347
EVSLC-MF 100119011502406951170632904x1601030x1503/4''F16/20456
EVSLC-MF 120148014402406951460632905x1601320x1503/4''F16/20567

Price List

Each unit requires a remote electronic controller per zone if the environment needs to be managed with different setpoint temperatures within the same season. Alternatively, if the same setpoint is desired for a large space, only one remote electronic controller is needed.

ModelsEurEVCNV2-N - BlackEVCNV2 -B - WhiteEVCNW2-N - Wi-Fi - BlackEVCNW2-B - Wi-Fi - WhiteReturn PlenumReplacement Filter2-Way On/Off Valve3-Way On/Off Valve
EVSLC-MF 601.902,89 230,88 230,88 285,05 285,05 206,74 53,55 293,17 356,09
EVSLC-MF 802.861,95 230,88 230,88 285,05 285,05 260,86 73,63 293,17 356,09
EVSLC-MF 1003.276,07 230,88 230,88 285,05 285,05 283,06 95,05 293,17 356,09
EVSLC-MF 1204.432,03 230,88 230,88 285,05 285,05 312,20 100,40 293,17 356,09

ModelsDescription
EVSLC-MF 60Return Plenum with 2 Circular Inlets for Flexible Duct ø 160 mm
EVSLC-MF 80Return Plenum with 3 Circular Inlets for Flexible Duct ø 160 mm
EVSLC-MF 100Return Plenum with 4 Circular Inlets for Flexible Duct ø 160 mm
EVSLC-MF 120Return Plenum with 5 Circular Inlets for Flexible Duct Ø 160 mm

Horizontal Installation

A: supply air
B: return air

 

Return Air Configuration

In EVSLC-MF units it is possible to vary the air intake port from rear to side.

 

Accessories for Air Return

 

Plant Example