EVBAC - EVBAF Batterie ad acqua per recuperatori serie terziario
Descrizione
Hydronic pre-/post-heating and cooling coil consisting of a galvanized steel frame, copper tubes and aluminum fins.
Structure equipped with male circular air connections with O-ring gasket to facilitate duct installation.
Threaded hydraulic connections complete with air vent and coil drain valves.
Hot Water Coil
Technical Specifications Models EVBAC1 EVBAC2 EVBAC3 EVBAC4 EVBAC5 Airflow (m3/h) 400 700-1000 1500-2000 2500-3500 3500-5000 Attacchi Idraulici 3/4”F 1”M 1”M 1”M 1”M DN
(Ø mm)250 315 355 400 500 H
(mm)240 420 470 570 820 L
(mm)290 440 590 640 640 W
(mm)500 500 500 500 500 Weight (kg) 5 8 11 13 17 Rated Thermal Power1 (kW) 4,18 9,37 19,32 21,46 38,80 Rated Water Flow1 (m³/h) 0,36 0,82 1,69 1,88 3,34 Pressure Drop – Water Side¹ (kPa) 10,80 13,40 21,60 25,90 18,50 Supply Air Temperature¹ (°C) 31,80 34,70 30,00 28,40 29,70 Rated Thermal Power2 (kW) 2,53 5,80 11,92 13,22 23,40 Rated Water Flow2 (m³/h) 0,22 0,50 1,03 1,15 2,00 Pressure Drop – Water Side¹ (kPa) 4,80 6,20 9,90 11,80 8,40 Supply Air Temperature2 (°C) 22,40 24,50 21,60 20,60 21,40 Pressure Drop – Air Side (Pa) 29 21 15 24 17 1Capacities and technical data refer to water inlet temperature 70°C, water outlet temperature 60°C, and inlet air temperature 8°C. 2Capacities and technical data refer to water inlet temperature 50°C, water outlet temperature 40°C, and inlet air temperature 8°C.
Schema
Price List – Hot Water Coil
Chilled Water Coil
Technical Specifications Models EVBAF1 EVBAF2 EVBAF3 EVBAF4 EVBAF5 Airflow (m3/h) 400 700-1000 1000-1500 1500-3000 3000-5000 Hydraulic Connections 1/2”M 1”M 1”M 1”M 1”M D
(mm)250 315 355 400 500 H
(mm)340 490 540 590 890 L
(mm)470 570 780 800 890 W
(mm)450 450 450 450 450 Weight (kg) 6 9 11 16 24 Rated Thermal Power1 (kW) 4,60 10,33 20,84 24,53 41,69 Rated Water Flow1 (m³/h) 0,81 1,80 1,81 2,14 3,63 Pressure Drop – Water Side¹ (kPa) 16,40 20,20 7,00 6,00 7,40 Supply Air Temperature¹ (°C) 34,50 35,10 31,80 31,30 31,70 Sensible Cooling Capacity² (kW) 5,59 12,70 8,19 9,56 16,44 Latent Cooling Capacity 2 (kW) 2,46 5,56 18,71 21,76 37,65 Rated Water Flow2 (m³/h) 0,91 2,20 3,21 3,74 6,46 Pressure Drop – Water Side¹ (kPa) 26,40 29,20 23,00 19,50 24,80 Supply Air Temperature2 (°C) 16,00 15,40 16,79 17,06 16,75 Pressure Drop – Air Side (Pa) 48 59 62 66 63 1Capacities and technical data refer to water inlet temperature 50°C, water outlet temperature 40°C, and inlet air temperature 8°C, 50% RH. 2Capacities and technical data refer to water inlet temperature 7°C, water outlet temperature 12°C, and inlet air temperature 27°C, 70% RH.