EVHRD EC Recuperator with dehumidification and air treatment from 300 to 500 m³/h with compressor and inverter
Description
The EVHRD EC is a controlled mechanical ventilation unit with heat recuperator and high efficiency inverter compressor, air treatment section with dehumidification, cooling and heating integration. The unit is equipped with plug-and - play solution for quick and simplified installation. The unit consists of a monoblock inclusive of each component for the proper operation and allows the operation with wide temperature range.
Characteristics
Perimeter structure self-supporting in galvanized sheet. Panels are made from double sandwich panel, with extrernhally painted finish. The insulation panel is made with high-performance insulation 23 mm thickness. Polypropylene exchanger in countercurrent high efficiency exceeding 90%. Summer and winter operation. Fans plug -fun brushless electronic motor and modulating control. High efficiency and low noise levels. Comply with Directive Erp. ePM1 filter easily removable on external air inlet and outlet on the air. Coarse filters with low pressure drop and easily removable on the air recirculation . Electrical panel on the unit with microprocessor and dedicated control. Refrigeration circuit with high efficiency inverter compressor.
Use
The unit is particularly suitable for residential, commercial or collective residential buildings where, in addition to the air exchange, it is necessary to dehumidify the presence of radiant systems.
Command electronics
Version K: Electrical panel on board unit with microprocessor and dedicated regulation. Fan management, display of internal machine temperature probes, timed dirty filter management, recirculation and renewal air management.
Possibility to control the unit with these three solutions:
- 1: Management through external commands and 0-10vdc signal to control air flow from minimum to maximum;
- 2: Management through remote panel with integrated T / H sensor;
- 3: MODBUS RTU RS 485 communication.
Accessories
- V2-1-EVHRD - 2-Way On/Off Water Valve 1/2";
- V3-1-EVHRD - 3-Way On/Off Water Valve 1/2";
- EVFHRDW - Kit Filtri;
- EDRM – Modulating Damper for Outdoor Air Intake.
Version
Version DC: version for dehumidification and integration in cooling / heating.
Unit for the renewal of the ambient air with the external one through a high efficiency recuperator, the air flow is increased by partially recirculating the ambient air thus allowing to dehumidify the air and to provide an integration of the cooling / thermal power radiant air conditioning system.
During the summer (active compressor) the unit can work in 2 modes:
Renewal + Dehumidification: The unit condenses partially in air and partially in water through the plate condenser, obtaining dehumidified air;
Renewal + Dehumidification + Cooling integration: The unit completely condenses in water, thus obtaining dehumidified and cooled air. During the winter period (compressor off) the hydronic battery is supplied with hot water from the heating system and behaves like a thermo-ventilator with recuperator.
Operation Only with Ventilation
The EVHRD unit will cater for mechanical ventilation with high efficiency heat recovery. It will be possible to select the fan speeds in order to obtain the desired flow rate to meet the air renewal requirements.
The selectable flow rates are:
On size EVHRD EC 30-15 from 0 to 150 m³/h.
On size EVHRD EC 50-25 from 0 to 250 m³/h.
Ventilation, Dehumidification and Integration Operation
The EVHRD EC unit will continue to satisfy mechanical ventilation with high efficiency heat recovery but will increase the air flow, recirculating from a dedicated room air duct to increase the air volume on the integration part.
The integration part consists of a version
with dehumidification and integration and hydronic integrative batteries.
It finds its most common application in radiant systems where there is a need for dehumidification and the integration of cooling in the summer period. During operation, the unit uses humidity and temperature probes to activate the refrigeration circuit composed of the compressor, the air evaporation coil and the air and water condenser powered by the radiant system, thus realizing the dehumidification of the air and the integration of cooling.
In the winter period, it is however possible to use the unit to integrate the radiant heating by feeding the hydronic hot water battery, obtaining a rapid heat input to the room.
Unit performance - General data
(1) Temperatura aria esterna 7°; umidità relativa 72%. temperatura ambiente 20°C; umidità relativa 28%, portata aria nominale
| Horizontal Version | Vertical Version | ||||
| Size EVHRD EC | 30/15 | 50/25 | 30/15 | 50/25 | |
| Efficienza nominale invernale recuperatore (1) | % | 85,7 | 86 | 83,9 | 86 |
| Nominal Outdoor Airflow Rate | m³/h | 154 | 265 | 161 | 258 |
| Total Airflow Rate | m³/h | 297 | 520 | 302 | 538 |
| Model classification according to European Regulation 1253/2014 and 1254/2014 | B | A | B | A | |
Technical Features
(1) External air temperature 33°; relative humidity 50%. room temperature 25°C; relative humidity 50%, water temperature 16°. nominal air and water flow.
(2) External air temperature 33°; relative humidity 50%. room temperature 25°C; relative humidity 50%, water temperature 16°. nominal air and water flow.
(3) Ambient temperature 20°C; relative humidity 50%, nominal air flow; Water at 35°C.
EVHRD EC Horizontal Vertical 30/15 50/25 30/15 50/25 Net Dehumidification Capacity (excluding the enthalpy content of outdoor air) (1) l/24h 75 99 75 99 Total Cooling Capacity2 kW 3,3 4,35 3,3 4,35 Compressor Power Consumption kW 0,88 1,06 0,88 1,06 Compressor Operating Frequency Hz 68 80 68 80 EER 3,71 4,1 3,71 4,1 Sensible Cooling Capacity (available upon integration phase completion) kW 1,4 1,91 1,4 1,91 Delivered Heating Capacity3 kW 0,7 1,25 0,7 1,25 Water Flow Rate m3/h 0,15 0,2 0,15 0,2 Pressure Drop Kpa 12 9 12 9 Sound Pressure Level Lp at 3 m dB(A) 41,6 42,9 41,0 41,4 V/Ph/Hz 230/1/50 230/1/50 Maximum Operating Current Draw A 4,7 5,9 4,7 5,9 Maximum Operating Power Consumption kW 1,02 1,27 1,02 1,27 Maximum Current Draw – Components A 7,5 8,1 7,5 8,1 Potenza massima assorbita componenti kW 1,61 1,73 1,61 1,73
Dimensions Orizzontal Versions
Dimensions EVHRD EC Horizontal Version 30/15 50/25 Larghezza A mm 1220 1220 Depth B mm 820 960 Altezza C mm 255 330 Recirculation Air Inlet DN1 mm 160 200 Extract Air Inlet DN2 mm 125 160 Fresh Air Inlet DN3 mm 125 160 Exhaust Air Outlet DN4 mm 125 160 Supply Air Outlet (G × H) mm 347x177 518x252 Water Connections – Supply / Return Ø 1/2"-1/2" 1/2"-1/2" Water Connection Diameter Ø 20 20
Dimensions Vertical Versions
Dimensions EVHRD EC Vertical Version EVHRD 30/15 EVHRD 50/25 Width L mm 885 985 Width W mm 515 740 Height H mm 1085 1185 Recirculation Air Inlet DN1 mm 160 200 Extract Air Inlet DN2 mm 125 160 Fresh Air Inlet DN3 mm 125 160 Exhaust Air Outlet DN4 mm 125 160 Mandata mm 347x177 518x252 Water Connections – Supply / Return Ø 1/2"-1/2" 1/2"-1/2" Water Connection Diameter Ø 20 20
Price Recovery and Accessories - Version K
Models Eur Accessories EVCNU - Remote Electronic Controller EVCNU - Remote Electronic Controller V2-1-EVHRD - 2-Way 1/2" On/Off Water Valve V3-1-EVHRD - 3-Way 1/2" On/Off Water Valve EVFHRDW-H - Filter Kit EDRM - Modulating Damper for Outdoor Air Intake EVCNU EVCNU-2 Eur Eur Eur Eur Eur Horizontal EVHRD EC 30/15 7.127,33 296,66 503,03 311,90 363,89 92,73 734,76 EVHRD EC 50/25 7.747,33 296,66 503,03 311,90 363,89 101,62 778,29 Vertical EVHRD EC 30/15 7.756,56 296,66 503,03 311,90 363,89 92,73 734,76 EVHRD EC 50/25 8.376,56 296,66 503,03 311,90 363,89 101,62 778,29
Price List – Insulated Supply Air Plenum
All dimensions are espressed in mm.