Description

The EVHRD is a unit of controlled mechanical ventilation with heat recovery unit high efficiency, air treatment section with dehumidification, cooling and heating . The unit is equipped with plug-and - play solution for quick and simplified installation. The unit consists of a monoblock inclusive of each component for the proper operation and allows the operation with wide temperature range.

Characteristics

Perimeter structure self-supporting in galvanized sheet. Panels are made from double sandwich panel, with extrernhally painted finish. The insulation panel is made with high-performance insulation 23 mm thickness. Polypropylene exchanger in countercurrent high efficiency exceeding 90%. Summer and winter operation. Fans plug -fun brushless electronic motor and modulating control. High efficiency and low noise levels. Comply with Directive Erp. ePM1 filter easily removable on external air inlet and outlet on the air. Coarse filters with low pressure drop and easily removable on the air recirculation . Electrical panel on the unit with microprocessor and dedicated control. Cooling circuit with high efficiency compressor.

Command electronics

Version K: Electrical panel on board unit with microprocessor and dedicated regulation. Fan management, display of internal machine temperature probes, timed dirty filter management, recirculation and renewal air management.

 Possibility to control the unit with these three solutions:

  • 1: Management through external commands and 0-10vdc signal to control air flow from minimum to maximum;
  • 2: Management through remote panel with integrated T / H sensor;
  • 3: MODBUS RTU RS 485 communication.

Use

The unit is particularly suitable for residential, commercial or collective residential buildings where, in addition to the air exchange, it is necessary to dehumidify the presence of radiant systems.

Versions

Version D: version for dehumidification with neutral air (isothermal).
Unit for the renewal of the ambient air with the external one through a high efficiency recuperator, the air flow is increased by partially recirculating the ambient air thus allowing the operation of the refrigeration circuit, obtaining during the summer period (compressor active) dehumidified air .
Equipped with a post-cooling / heating hydronic battery which, if supplied, provides a supplement to the cooling / heating capacity of the radiant air-conditioning system (the connection to the heating / cooling system is optional and does not affect air dehumidification).

Version DC: version for dehumidification and integration in cooling / heating.
Unit for the renewal of the ambient air with the external one through a high efficiency recuperator, the air flow is increased by partially recirculating the ambient air thus allowing to dehumidify the air and to provide an integration of the cooling / thermal power radiant air conditioning system.
During the summer (active compressor) the unit can work in 2 modes:
Renewal + Dehumidification: The unit condenses partially in air and partially in water through the plate condenser, obtaining dehumidified air;
Renewal + Dehumidification + Cooling integration: The unit completely condenses in water, thus obtaining dehumidified and cooled air. During the winter period (compressor off) the hydronic battery is supplied with hot water from the heating system and behaves like a thermo-ventilator with recuperator.

Operation Only with Ventilation

The EVHRD unit will cater for mechanical ventilation with high efficiency heat recovery. It will be possible to select the fan speeds in order to obtain the desired flow rate to meet the air renewal requirements.
The selectable flow rates are:
On size EVHRD 30-15 from 0 to 150 m³/h
On size EVHRD 50-25 from 0 to 250 m³/h

 

Ventilation, Dehumidification and Integration Operation

The EVHRD unit will continue to satisfy the mechanical ventilation with high efficiency heat recovery but will increase the air flow rate, recirculating from a dedicated ambient air duct to increase the air volume on the integration part.
The integration part can consist of a version
with dehumidification (Version D), from a version with dehumidification and integration (Version DC) and hydronic supplementary batteries.
The D version, finds its most common application, in radiant systems where there is the need of only dehumidification in the summer. During operation, the unit, through humidity and temperature probes, activates the refrigerant circuit composed of the compressor, the air evaporation coil and the air condenser, thus performing dehumidification. It is possible to supply the hydronic post battery with the radiant system water (the lack of battery power does not compromise the operation of the refrigeration circuit) it is possible to integrate it with the summer cooling and the winter heating.
The DC version, finds its most common application, in radiant systems where there is the need for dehumidification and the integration of cooling in the summer. During operation, the unit, through humidity and temperature probes, activates the refrigerant circuit composed of the compressor, the air evaporation coil and the air and water condenser supplied by the radiant system, thus achieving air dehumidification and integration. cooling.
In winter, it is still possible to use the unit to integrate the radiant heating by feeding the hot water hydronic battery, obtaining a rapid thermal contribution to the environment.

 

Unit Performance - General Data

(1) Temperatura aria esterna 7°; umidità relativa 72%. temperatura ambiente 20°C; umidità relativa 28%, portata aria nominale.

  Horizontal VersionVertical Version
Size EVHRD 30/15EVHRD 50/25EVHRD 30/15EVHRD 50/25
Efficienza nominale invernale recuperatore (1)%85,78683,986
Nominal Outdoor Airflow Ratem³/h154265161258
Total Airflow Ratem³/h297520302538
Model classification according to European Regulation 1253/2014 and 1254/2014BABA

D Version

(1) Outdoor air temperature 30°C; relative humidity 60%. Room temperature 25°C; relative humidity 50%; nominal airflow rate.
(2) Room temperature 25°C; relative humidity 60%; nominal airflow rate; water inlet 16°C, water outlet 18°C.
(3) Room temperature 20°C; relative humidity 60%; nominal airflow rate; water inlet 35°C, water outlet 30°C.

Version D Horizontal VersionVertical Version
 EVHRD 30/15EVHRD 50/25EVHRD 30/15EVHRD 50/25
Net Dehumidification Capacity (excluding the enthalpy content of outdoor air) (1)l/24h30,55630,556
Cooling Capacity Delivered by Hydronic CoilkW0,71,560,71,56
Water Flow Ratem³/h0,250,350,250,35
Pressure DropKpa8,510,58,510,5
Delivered Heating Capacity3kW0,861,40,861,4
Sound Pressure Level Lp at 3 mdB(A)40,840,940,840,9
Power SupplyV/Ph/Hz230 / 1 / 50
Maximum Absorbed CurrentA5,575,57

DC Version

(1) Outdoor air temperature 30°C; relative humidity 60%. Room temperature 25°C; relative humidity 50%; nominal airflow rate.
(2) Room temperature 25°C; relative humidity 60%; nominal airflow rate; water inlet 16°C, water outlet 18°C.
(3) Room temperature 20°C; relative humidity 60%; nominal airflow rate; water inlet 35°C, water outlet 30°C.

Version DC Horizontal VersionVertical Version
 EVHRD 30/15EVHRD 50/25EVHRD 30/15EVHRD 50/25
Net Dehumidification Capacity (excluding the enthalpy content of outdoor air) (1)l/24h30,55630,556
Cooling Capacity Delivered by Compressor (2)kW1,552,41,552,4
Cooling Capacity Delivered by Hydronic CoilkW0,71,560,71,56
Water Flow Ratem³/h0,250,350,250,35
Pressure DropKpa8,510,58,510,5
Delivered Heating Capacity3kW0,861,40,861,4
Sound Pressure Level Lp at 3 mdB(A)40,840,940,840,9
Power SupplyV/Ph/Hz230 / 1 / 50
Maximum Absorbed CurrentA5,575,57

Dimensions Orizzontal Versions

DimensionsHorizontal Version
EVHRD 30/15EVHRD 50/25
Larghezza Amm12201220
Depth Bmm820960
Altezza Cmm255330
Recirculation Air Inlet DN1mm160200
Extract Air Inlet DN2mm125160
Fresh Air Inlet DN3mm125160
Exhaust Air Outlet DN4mm125160
Supply Air Outlet (G × H)mm347x177518x252
Water Connections – Supply / ReturnØ1/2"-1/2"1/2"-1/2"
Water Connection DiameterØ2020

Dimensions Vertical Versions

DimensionsVertical Version
EVHRD 30/15EVHRD 50/25
Width Lmm885985
Width Wmm515740
Height Hmm10851185
Recirculation Air Inlet DN1mm160200
Extract Air Inlet DN2mm125160
Fresh Air Inlet DN3mm125160
Exhaust Air Outlet DN4mm125160
Mandatamm347x177518x252
Water Connections – Supply / ReturnØ1/2"-1/2"1/2"-1/2"
Water Connection DiameterØ2020

Price Recovery and Accessories - Version K

 ModelsHeat Recovery Unit VersionAccessories
DDCEVCNU - Remote Electronic ControllerEVCNU - Remote Electronic ControllerV2-1-EVHRD - 2-Way 1/2" On/Off Water ValveV3-1-EVHRD - 3-Way 1/2" On/Off Water ValveFilter Kit
EVCNUEVCNU-2
EurEurEurEurEurEurEur
HorizontalEVHRD 30/155.564,55 5.944,78 296,66 503,03 311,90 363,89 92,73
EVHRD 50/256.241,21 6.572,65 296,66 503,03 311,90 363,89 101,62
VerticalEVHRD 30/156.164,91 6.545,14 296,66 503,03 311,90 363,89 92,73
EVHRD 50/256.977,89 7.309,34 296,66 503,03 311,90 363,89 101,62

Price List – Insulated Supply Air Plenum

All dimensions are espressed in mm.

ConfigurazioneModelsLHPØEur
HorizontalEVHRD 30/153471771001x16066,30
EVHRD 50/255182521002x160101,87
VerticalEVHRD 30/153471771001x16066,30
EVHRD 50/255182521002x160101,87