Description

The EVHRDS EC is a compact INVERTER-driven unit for Controlled Mechanical Ventilation systems with a dehumidification section and cooling and heating integration. The unit is supplied as a plug-and-play solution for quick and easy installation. The unit consists of a one-piece structure including every component for correct operation with wide temperature ranges.

Characteristics

Painted sheet metal self-supporting perimeter structure. The panels are insulated with 6 mm thick polyethylene. Dual-suction fans with Brushless EC motor. Very high efficiency and low noise levels in accordance with Erp regulations. Coarse filters with low pressure drop easily removable on the recirculation air. Cooling circuit made of brazed copper complete with: high efficiency compressor, filter drier, finned coils, water exchanger, solenoid valves, throttling device, liquid receiver, high pressure switches.

Use

The unit is particularly suitable for residential, commercial or collective residential buildings where dehumidification is required in addition to air exchange due to the presence of radiant systems.

Command electronics

Version K: On-board electrical panel with microprocessor and dedicated control. Fan management, motorised recirculation damper management, timed dirty filter management, recirculation and fresh air management.

Possibility of controlling the unit with these three solutions:

  • 1: management via external controls and 0...10vdc signal for air flow rate control from minimum to maximum;
  • 2: management via EVCNU remote panel with built-in T/H sensor;
  • 3: MODBUS RTU RS 485 communication.

Accessories

  • V2-1-EVHRD - 2-Way On/Off Water Valve 1/2";
  • V3-1-EVHRD - 3-Way On/Off Water Valve 1/2";
  • EVFHRDS - Filter Kit (for Recirculation Versions Only);
  • EPIV - Insulated Supply Air Plenum.

Versions DC

Version DC all outside air: unit for the dehumidification of the air coming from the heat recovery unit and for the cooling/heating integration to the radiant air conditioning system.
During summer (compressor on) the unit can operate in 2 modes:
- dehumidification: the unit condenses partially in air and partially in water by means of the plate condenser, obtaining dehumidified air;
-dehumidification + Cooling integration: the unit condenses completely in water, thus obtaining dehumidified and cooled air.
During winter (compressor off), the water coil is supplied with hot water from the heating system and behaves like a fan coil with heat recovery unit.
Models:
- EVHRDS EC 30 H K DC
- EVHRDS EC 50 H K DC

Version DC outside air and recirculation: unit for the dehumidification of the air coming partially from the heat recovery unit and partially from the indoor environment, with cooling/heating integration to the radiant air conditioning system.
During summer (compressor on) the unit can operate in 2 modes:
- dehumidification: the unit condenses partially in air and partially in water by means of the plate condenser, obtaining dehumidified air;
-dehumidification + Cooling integration: the unit condenses completely in water, thus obtaining dehumidified and cooled air.
During winter (compressor off), the water coil is supplied with hot water from the heating system and behaves like a fan coil with heat recovery unit.
- EVHRDS EC 30 H R K DC
- EVHRDS EC 50 H R K DC

General Data

Size Horizontal Configuration
EVHRDS EC 30EVHRDS EC 50
Power SupplyV/Ph/Hz230/1/50
Ingress Protection (IP) ratingIP20
Total Airflow Ratem3/h300500
Nominal Outdoor Airflow Rate (R versions with recirculation)m3/h130190
Pressure Drop – VMC SidePa3138
Rated Power Consumption of Recirculation FankW0,10,1

Versions DC

(1) Outside air temperature 33°C; relative humidity 50%. room temperature 25°C; relative humidity 50%, water temperature 16°C. Nominal air and water flow rates.
(2) Outside air temperature 33°C; relative humidity 50%. room temperature 25°C; relative humidity 50%, water temperature 16°C. Nominal air and water flow rates.
(3) Room temperature 20°C; relative humidity 50%, nominal air flow rate; Water in 35°C.

Version DC EVHRD EC 30EVHRD EC 50
Net Dehumidification Capacity1l/24h5689
Total Cooling Capacity2kW2,63,95
Compressor Power ConsumptionkW0,690,95
Compressor Operating FrequencyHz5573
EER 3,754,15
Sensible Cooling CapacitykW1,181,69
Delivered Heating Capacity3kW0,531,15
Water Flow Ratem3/h0,120,18
Pressure DropKpa97
Sound Pressure Level Lp at 3 mdB(A)39,540,8
Electrical SupplyV/Ph/Hz230/1/50
Maximum Operating Current DrawA3,75,1
Maximum Operating Power ConsumptionkW0,791,11
Maximum Current Draw – ComponentsA6,787
Maximum Power Consumption – ComponentskW1,491,55

Dimensions

DimensionsEVHRDS EC 30EVHRDS EC 50
Larghezza Amm690690
Depth Bmm690800
Altezza Cmm270320
Recirculation Air Inlet DN1 (not available in non-recirculation version)mm160200
Primary Air Inlet (from ventilation unit) DN2mm160200
Supply Air Outlet (b × h)mm347x177518x252
Water Connections – Supply / ReturnØ"1/2” - 1/2”1/2” - 1/2”
Water Connection DiameterØ mm1212
Unit Weight DCkg4356
Weight – R DC Versionkg4657

Supply Plenum Dimensions

All dimensions are expressed in mm.

ModelsLHPØ
EVHRDS EC 303471771001x160
EVHRDS EC 505182521002x160

Heat Recovery Units and Accessories Price List - Version K

ModelsNon-Recirculation VersionsRecirculation VersionAccessories
DCR DCEVCNU - Remote Electronic ControllerV2-1-EVHRD - 2-Way 1/2" On/Off Water ValveV3-1-EVHRD - 3-Way 1/2" On/Off Water ValveEVFHRDS – Filter Kit (for Recirculation Versions Only)EPIV – Insulated Supply Air Plenum
EurEurEurEurEurEurEur
EVHRDS EC 303.799,99 4.174,16 296,66 311,90 363,89 36,94 66,30
EVHRDS EC 504.078,35 4.452,52 296,66 311,90 363,89 45,14 101,87