Description

Active recovery unit for heating, cooling and room air renewal. The unit is composed of a monobloc including all components for correct operation: fans, refrigeration circuit with high efficiency compressors, air filtration sections and cross-flow heat recovery unit.

Characteristics

Panels made by double sandwich panel 38 mm thickness, with externally white painted finish and Aluzinc inside the unit. Perimeter structure with aluminium profiles, with seals and no air leakage. The insulation of the panels is made with high performance insulation which allows low noise and reduced transmittances during unit operation. Coss-flow aluminium heat exchanger has an efficiency of 50-60%. Summer and winter operation. Double suction centrifugal fans with directly coupled motor compliant with Erp regulations. The thermodynamic recovery allows, thanks to its refrigeration circuit, to supply energy to the environment in a greater quantity than that subtracted from ventilation. Upstream of the recovery unit there are two filters with easily removable ePM1 70-80% filtration class. Refrigerant circuit made of brazed copper complete with: high efficiency compressor, dehydrating filter, finned batteries, solenoid valves, electronic expansion valve, receiver liquid, pressure transducers and safety devices. On-board electrical panel with microprocessor and dedicated regulation. Fan management, visualization of internal temperature probes, temporized dirty filters management. Defrost algorithm management optimized for operation with low internal temperatures. Wide graphical interface with configuration menu and multi-lingual user menu. Predisposition for MODBUS RTU RS 485 communication with the most varied home automation systems.

Unit components

Refrigeration Circuit:

  • high-efficiency rotary or scroll compressor;
  • copper tube coils with aluminum fins;
  • 4-way reversing valve;
  • electronic expansion valve;
  • filter drier;
  • pressure transducers;
  • liquid receiver;
  • high-pressure switch and safety devices.

Air Handling Circuit:

  • cross-flow aluminum heat recovery exchanger;
  • double-inlet centrifugal fans;
  • ePM1 70–80% filters.

Electrical Circuit:

  • main disconnect switch;
  • protection fuses;
  • contactors and relays;
  • microprocessor controller.

Use

EVHRA works as a passive recuperator and as an active thermodynamic recuperator and is particularly suitable for residential, commercial or collective residential buildings, it has plug-and-play for a quick and simplified installation.

Accessories

  • EVBE - ON/OFF duct electric heater.
  • EVBER - Duct electric heater with integrated control.
  • EVBAC - Pre-heating or post-heating coil.
  • EVBAF - Pre-cooling or post-cooling coil.

Possible Configurations - Left-Hand Version

- if not expressly indicated in the order, the configuration produced will be H1SX.

 

Configurazioni Possibili - Versione DX

- if not expressly indicated in the order, the configuration produced will be H1DX.

 

General Technical Data

(1) Outdoor air -5 ° / 80% RH - Indoor air 20 ° / 50% RH - Nominal flow rate.
(2) data referred to 3 meters of free field distance.

Models  60100150250350500
Fan Type Centrifughi a doppia aspirazione
Number of Fans 2
Nominal Air Flowm³/h60010001500250035005000
Available Static Pressure - Fresh Air SidePa200200170180100200
Available Static Pressure - Exhaust Air SidePa12418013014085200
Compressor Type Rotativo ad alta efficienzaScroll ad alta efficienza
Refrigerant Type R410A
Passive Heat Recovery Unit Piastre in alluminio a flussi incrociati
Minimum Heat Recovery Efficiency (1)%5550,550,153,752,651,3
Filters ePM1 70-80%
Maximum Fan Power ConsumptionkW0,70,740,741,11,53
Maximum Fan Current DrawA3,15,25,27,815,610
Maximum Compressor Power ConsumptionkW1,061,832,895,047,239,39
Maximum Compressor Current DrawA4,758,5713,88,612,215,9
Supply VoltageV/ph/Hz230/1ph/50400/3ph/50
Maximum Total Power ConsumptionkW1,762,573,636,148,7312,39
Maximum Total Current DrawA7,8513,71916,427,825,9
Ingress Protection (IP) ratingIP202020202020
Sound Pressure Level2dB(A)485354566168
Dimensions 60100150250350500
WidthWmm140016801800196019602240
DephtLmm92512501250143014301610
HeightHmm415515515620720920
Air ConnectionsDNØ mm200315315355400500
Condensate Drain ConnectionsØ mm202020202020
Weightkg140230278325382570

Technical Data Winter Operation

(1) Outdoor air -5 ° / 80% RH - Indoor air 20 ° / 50% RH - Nominal flow rate.

Models 60100150250350500
Passive Heat Recovery
Heating Capacity (1)kW2,34,226,2311,215,422,4
Active Heat Recovery
Heating Capacity (1)kW2,825,037,971318,224,4
Power InputkW0,581,121,632,73,45,2
COP 4,864,494,884,815,354,69
Total Heat Recovery
Overall COP 8,828,258,718,969,889
Supply Air Temperature°C22,121,922,523,222,622,1
Heating Capacity (1)kW5,129,2514,224,233,646,8

Technical Data for Summer Operation

(1) Outdoor air 30 ° / 60% RH - Indoor air 25 ° / 50% RH - Nominal flow rate.

Models 60100150250350500
Passive Heat Recovery
Cooling Capacity (1)kW0,40,761,132,082,854,22
Active Heat Recovery
Cooling Capacity (1)kW2,685,328,112,7118,425,1
Power InputkW0,791,292,23,895,57,3
EER 3,394,123,683,263,343,43
Total Heat Recovery
Overall EER 3,84,714,193,83,864
Supply Air Temperature / Humidity°C / Ur%19,7 / 87,219,6 / 87,919,8 / 86,319,9 / 8619,9 / 86,919,9 / 85
Cooling Capacity (1)kW3,086,089,2314,7921,2529,32

Operating Limits

Size  60100150250350500
Riscaldamento Aria InternaAria Esterna
°C15 / 25°C-20 / 20°C
Raffrescamento Aria InternaAria Esterna
°C18 / 28°C15 / 40°C

Heat Recovery Units and Accessories Price List

ModelsEVHRA-SXEVHRA-DXEVTGFEVSATT-EVHRAEVFHRA - Filter Kit
 EurEurEurEurEurEur
6011.678,11 12.145,03 472,17 144,37 295,49 168,95
10014.818,84 15.404,42 472,17 144,37 399,46 344,25
15015.879,08 16.509,81 472,17 144,37 532,15 344,25
25018.941,13 19.691,81 472,17 144,37 697,68 646,58
35019.996,21 20.797,20 472,17 144,37 822,17 522,09
50027.607,49 28.712,87 472,17 144,37 1.027,37 964,15