EVTD ATEX Centrifugal fan for circular duct ATEX
Description
Low profile in-line mixed flow duct explosion proof fans. TD-800 Ex is manufactured in antistatic plastic material. The others models are manufactured from sheet steel protected with black polyester paint coating. Detachable fan unit without demounting duct connections.
Characteristics
Explosion proof versions in accordance with ATEX Directive, for single phase 230V-50Hz. Motors IP44, Class B.
For ambient working temperatures from -20ºC to +40ºC.
ATEX Increased safety:
- For model 800: II2G EExeIIT3 EC: LOM 08 ATEX 2052 X Supplement 2.
- For models 1100 and 1200: II2G EExeIIT3 Gb EC: LOM 11 ATEX 2021 X Supplement 1. See data for selection, or refer to Easyvent.
Use
Accessories
- Fitting for rectangular duct.
- Security mesh.
Note
EVTD ATEX non può esser regolato da regolatore di velocità.
Dimensions
all measurements are in mm.
Models A B C ØD E F G H I EVTD 800/200-ATEX 302 255 232,5 198 140 100 94 124 275,6 EVTD 1100/250-ATEX 386 324 291 248 168 145 140 155 339 EVTD 1200/315-ATEX 450 392 356 312 210 182 178 188 371
Operating data
Models Velocity r.p.m. Maximum Input Power Maximum Input Current Maximum Airflow Acoustic Pressure Level* (dB(A)) ø Duct W A m3/h Aspirazione Irradiato Espulsione mm EVTD 800/200-ATEX 2450 120 0,50 1.020 53 43 55 200 EVTD 1100/250-ATEX 2630 197 0,81 1.130 59 46 65 250 EVTD 1200/315-ATEX 2600 170 0,71 1.320 56 44 59 315
Operating Temperature and Weight
| Models | Operating Temperature Range | Weight |
| °C | Kg | |
| EVTD 800/200-ATEX | -20/+40 | 5 |
| EVTD 1100/250-ATEX | -20/+40 | 20 |
| EVTD 1200/315-ATEX | -20/+40 | 25 |
Performance Data
Models Airflow 0 Pa 40 Pa 80 Pa 100 Pa 150 Pa 200 Pa 250 Pa 350 Pa 400 Pa 500 Pa EVTD 800/200-ATEX 1020 950 900 880 790 220 EVTD 1100/250-ATEX 1130 1070 980 950 800 700 430 210 170 EVTD 1200/315-ATEX 1300 1220 1150 1100 980 820 630 410 320 190
Price List