EVKABT Self-cleaning ventilation box
Description
Cabinet fans manufactured from galvanised steel sheet with double thickness side panels lined with 17 mm thickness of fireproof fibreglass acoustic insulation (M0). Circular duct connection flange on the inlet.
EVKABB / EVKABT incorporates direct driven aluminium backward curved centrifugal impeller with motor fitted outside of the air stream. Supplied with galvanized drip tray and copper drain.
Features
Supply voltage: Trhree fase 230/400V-50Hz or 400V-50Hz.
It is possible to adjust the speed of fans with frequency inverter (optional).
Working temperature range: -20ºC A +100ºC.
Dimensions
All measurements are expressed in mm.
Model A B C øD E F G H J K L M N (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) EVKABT/4-3000/315 505 549 445 315 421 325 125 253 198 222 90 100 12 EVKABT/4-4000/355 550 592 490 355 466 370 170 275 222 245 60 100 12 EVKABT/4-6000/450 630 674 570 450 546 450 130 315 242 265 60 160 12 EVKABT/4-9000/500 710 753 630 500 606 510 190 355 271 294 100 206 8 EVKABT/4-12000/560 800 844 720 560 696 600 182 400 343 366 100 209 8
Technical Features
* Sound pressure level measured at 1,5m, in free field condition, at the medium point of the performance curve
Model Speed
Maximum Power Consumption Maximum Current Draw Airflow Acoustic Pressure Level* Weight Frequency Converters – Optional – 400V 3-Phase Supply 230 V 400 V Suction Radiated Discharge Model Kw RPM kW A m3/h dB(A) kg EVKABT/4-3000/315 1430 327 1,2 0,7 2.750 60 54 61 33 M130L 0,75 EVKABT/4-4000/355 1450 561 2,1 1,2 4.000 63 55 65 40 M130L 0,75 EVKABT/4-6000/450 1495 1221 5,4 3,1 6.350 67 55 71 58 M130M 1,5 EVKABT/4-9000/500 1430 2022 6,1 3,5 8.840 76 62 77 75 M130M 1,5 EVKABT/4-12000/560 1460 2673 - 5 11.400 71 59 75 120 M130P 2,2
Aeraulic performance three-phase 400V models
Model Static Pressure 50 Pa 100 Pa 150 Pa 200 Pa 250 Pa 300 Pa 350 Pa 400 Pa 450 Pa 500 Pa 550 Pa Airflow at 50hz (m3/h) EVKABT/4-3000/315 2600 2400 2200 1980 1780 1600 1350 1050 400 - - EVKABT/4-4000/355 3800 3650 3500 3320 3200 2850 2600 2300 2000 1100 300 EVKABT/4-6000/450 5900 5800 5500 5350 5070 4850 4600 4400 4150 3800 3500 EVKABT/4-9000/500 8500 8400 8050 7800 7550 7400 7050 6900 6700 6400 6000 EVKABT/4-12000/560 11300 11100 10900 10600 10400 10000 9600 9450 9050 8700 8250
Model Static Pressure 600 Pa 650 Pa 700 Pa 750 Pa 800 Pa 850 Pa 900 Pa 950 Pa 1000 Pa Airflow at 50hz (m3/h) EVKABT/4-3000/315 - - - - - - - - - EVKABT/4-4000/355 - - - - - - - - - EVKABT/4-6000/450 2600 1800 500 - - - - - - EVKABT/4-9000/500 5800 5450 5000 4500 3750 2800 1100 400 - EVKABT/4-12000/560 8000 7300 6700 6250 6000 5500 4700 3500 2250
Outdoor cover EVCTIKABT
For outdoor installations.
All measurements are expressed in mm.
Model A B a b (mm) (mm) (mm) (mm) EVKABT 3000 535 535 325,2 420,7 EVKABT 4000 580 580 370 465,5 EVKABT 6000 660 660 450 545,5 EVKABT 9000 740 740 510 605,5 EVKABT 12000 830 830 600 695,5